Product

ASHOK LEYLAND AL 4 Series - LP30 (30KVA) Generator

 

Description

LEYPOWER Power Solutions is the fastest growing genset provider in India. With state-of-the-art technology in engine, alternator and controllers, LEYPOWER provides a fully integrated power system at par with global standards at a very competitive overall cost of ownership.

LEYPOWER ready-to-use diesel generating sets meet with the latest CPCB norms in India and built to comfortably meeting international norms. These sets are powered by the compact 4, 6, 8 and 12 cylinder series of diesel engines. Aesthetically designed, these DG sets are silent, environment-friendly require minimum maintenance and are low on operating costs.

Leypower diesel generating sets are manufactured in the state-of-the-art plants located across 6 units in the country using the latest machinery and skill sets to roll out well engineered DG sets.

The present range extends from 10-2250 kVA with generating sets manufactured to operate under arduous conditions.

SPECIFICATION
parameters description
Power Rating (KVA) 30
Electric Power (KWe) 24
Rated Current (A) 41.6
No of Phases/Volts* 3/415
Oveall Dimensions (L X W X H, mm x mm x mm) 2000 x 950 x 1390
Fuel Tank Capacity (Litres) 50 / 60
Battery Capacity (AH) 99
System Voltage (VDC) 12
Weight (Kg) 744
Dry Weight (Engine-Kg) 220
ENGINE SPECIFICATION
Parameters Description
Engine Model AL 485TAG4
Engine Max HP 48.3
Engine Rated HP 44.6
Aspiration TA
No of Cylinders 4
Bore & Stroke (mm x mm) 85*92
Displacement (Litres) 2.088
Compression Ratio 18:01:00
Lub oil Sumb Capacity (Litres) 8.5
Lub oil Consumption 0.0113
Coolant Capacity (Litres) 9
Governing Class A1
ALTERNATOR SPECIFICATION
Parameters Description
Model P 14G1
Type 4 pole
Exciter type Brushless
Voltage regulator AVR-AS480
Insulation Class H
Temperature rise (ºC) 125
Bearing ±Single
Voltage regulation ±0.5%
Rated Voltage (V) 415
SPECIFICATION FOR STANDARD MANUAL PANEL
Parameters Description
SWITCH GEAR 3pole MCB / MCCB
Analogue Gauge
  • Water Temperature

  • Lube Oil Pressure

  • Engine RPM

  • Battery Charging Ammeter

  • Running-Hour Counter

Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
  • Low Oil pressure

  • Battery Charger Failure

  • High Engine Temperature

  • Low fuel level

Current Transformers of suitable rating
Indications (LED):
  • DG ON

  • Load on DG

Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Parameters Description
SWITCH GEAR
  • 4 Pole Contactor for DG

  • 4 Pole Contactor for MAINS

  • MCB / MCCB for short circuit protection

Features
  • Monitoring of engine protection

  • Alphanumeric LCD Display

  • Supervision of Mains and DG voltage

  • Mains and DG contactor interlock

  • Provision for Remote start / stop

  • Parameter setting by front panel key board

  • Auto / Manual mode operation

  • Programmable parameters / timers

Multifunction meter
  • Voltage

  • Ampere

  • Frequency

Analogue meter
  • Oil pressure

  • Water Temperature

  • Engine RPM

Indication Lamps
  • Mains On

  • DG On

  • Load on Mains

  • Load on DG

POWER RATING
Parameters Description
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA -750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046

© 2016,Universal Electricals. All rights reserved. || Develop By :: Core Objects